وایبریشن سوئیچ متریکس SM6100

External accelerometer, velometer or velocity transducer
See option ‘G’ in SM6100 Datasheet (doc #1009514).
Sensor
Amplifier/ integrator to obtain velocity or displacement response. True RMS detection.Signal Conditioner
50g, peak; 4 ips, peak. See option “B” for vibration ranges in SM6100 Datasheet (doc # 1009514)Maximum Vibration Limit
(Vxducer) (gain X1) 2 Hz to 3000 Hz (-3 dB). Capable of driving 300 meters (1000 feet) of shielded cable (0.03uF max)Buffered Dynamic Signal
A green LED when illuminated indicates that the external sensor is connectedSensor OK Indicator
Single limit standard, second limit optional, Adjustable from -10% to 110% of range, 2% repeatabilityAlarm Limit(s)
Limit 1, amber LED; Limit 2, red LEDTrip Indicators
Fully adjustable time delay of 1 – 15 secondsLimit Trip Delay
250 VAC, 1A, optically isolated, field selectable N.O. or N.C. Factory set @ N.C. position. Holding current 35 mA maximum at 25°C (60 mA at -40°C)Triac Outputs
50 VDC, 0.5A, Field Selectable N.O. or N.C. Factory set @ N.COptional FET Output
Standard delay is fixed at 30 seconds. Optional remotely retriggerable startup delay adjustable from 1 – 30 secondsStartup Trip Delay
4-20mA proportional to velocity or displacement. See option “B” in SM6100 Datasheet (doc # 1009514). Zero and Span calibrated ±2%. Non-linearity less than 2%. 600 ohms max. load resistanceOptional 4-20 mA Source Output
2Kg, (4.4 lbs)Weight
Cast aluminum: Explosion-proof / weather proof. Stud mount: 1/2-14 NPT standard or optional M20 1.5 straight thread with jam nut. Other mountings availableHousing
3/4-14 NPT or M20 X 1.5 straight threadConduit connections
95 to 125 VAC, 190 to 250 VAC, 50/60 Hz, 5W max. or 20 to 28 VDC, 7W max. Power isolated from circuitsInput power
(vel)±3.0 dB 2 Hz to 3000 Hz
(disp)±3.0 dB 2 Hz to 200 Hz
Frequency Response
No Display: -40°C to +85°C, -20°C to +85°C (ATEX) w/Display: -10°C to +70°CTemperature Limits
Less than .05%/°C (calibrated at 25°C)Output Sensitivity vs Temperature
Alarm limit adjustment to below 0% of range causes triac / FET actuation.Alarm Test
Wire clamp type screw terminal block. Max. wire gauge: 14 AWG. 500 Vrms, circuit to case.Field Wiring
See option “D” in SM6100 Datasheet (doc # 1009514)Hazard Rating
NEMA 4/4X, IP 65Environmental Rating
CE tested to EN61326-1:2006Electromagnetic Compatibility
2 1/2digit LCD. Window provided only with display version.Optional Display
Standard internal switch, remote N.O. contacts or optional external switchReset